Datos relativos solo a combinación con interiores ecodan.
Modelo | Estándar | PUMY-P112V/YKM | PUMY-P125V/YKM | PUMY-P140V/YKM |
||
---|---|---|---|---|---|---|
Versión -BS | PUMY-P112V/YKM-BS | PUMY-P125V/YKM-BS | PUMY-P140V/YKM-BS |
|||
Tipo | Split R410A | |||||
Tecnología | City Multi | |||||
Capacidad | Calefacción | ATW (A7W35) | [kW] | 12,5 | ||
ATA | [kW] | 14,0 | 16,0 | 18,0 | ||
Refrigeración | ATA | [kW] | 12,5 | 14,0 | 15,5 | |
Datos de alimentación eléctrica | Alimentación | VKM : 1∿, 230V, 50Hz / YKM : 3∿, 400V, 50Hz |
||||
Corriente máx. | [A] | VKM : 29,5 / YKM : 12,0 |
||||
Tamaño PIA | [A] | VKM : 40A1) / YKM : 20A2) |
||||
Cableado | [mm²] | VKM : 2 × 16 + ⏚ / YKM : 4 × 4 + ⏚ |
||||
Datos de instalación | Dimensiones | Al×An×Fo | [mm] | 1338×1050×330 | ||
Peso | [kg] | VKM : 73 / YKM : 125 |
||||
Nivel sonoro | SPL (Calor) | [dB] | 51 | 52 | 53 | |
SPL (Frío ATA) | [dB] | 49 | 50 | 51 | ||
PWL (Calor) | [dB] | 71 | 72 | 73 | ||
Caudal del ventilador | [m³/min] | 110 | ||||
Datos frigoríficos | Diámetros Tuberías | Líquido | [mm (″)] | ⌀ 9,52 (⅜) | ||
Gas | [mm (″)] | ⌀ 15,88 (⅝) | ||||
Distancias máximas | Altura | [m] | 50m3) / 40m4) | |||
Total | [m] | Máx. 150m total / Máx. 80m por cada una. | ||||
Gas refrigerante | Tipo (PCA) | R410A (2088) | ||||
Precarga | [kg] | 4,8 | ||||
[m] | ||||||
Datos del circuito hidráulico primario | Tª impulsión | Calor (Máx.) | [°C] | 55 | ||
Caudal de trabajo | [ℓ/min] | 17,9 ~ 35,8 | ||||
Volumen mínimo | Cl. med/cál | [ℓ] | 27 | |||
Clima frío | [ℓ] | 80 | ||||
Rango de Tª exterior operativa | Refrigeración ATA | [°C] | -5 ~ +525) | |||
Calefacción ATA | [°C] | -20 ~ +21 | ||||
Calefacción ATW | [°C] | -20 ~ +21 | ||||
Producción ACS | [°C] | -20 ~ +35 | ||||
Unidades interiores compatibles | Hydrobox | S/C | EHSC-VM2D |
|||
Hydrobox Dúo | S/C | 200ℓ | EHST20C-VM2D |
|||
Accesorios compatibles | Tratamiento Blygold® | ATW-BLY-2VN |
||||
Deflector de salida de aire | PAC-SH96SG-E |
|||||
Guía de protección de viento | PAC-SH95AG-E |
|||||
Tapones/guía drenaje | PAC-SG61DS-E |
|||||
Bandeja centralizada drenaje | PAC-SH97DP-E |
|||||
Branch Box | Box de 3 puertos | PAC-MK34BC |
||||
Box de 5 puertos | PAC-MK54BC |
|||||
Kit de unión de dos Branch Box | MSDD-50AR-E |
Temperatura de impulsión [°C] | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
25 | 35 | 40 | 45 | 50 | 55 | 60 | |||||||||
Rég. | Tª | Cap. | COP | Cap. | COP | Cap. | COP | Cap. | COP | Cap. | COP | Cap. | COP | Cap. | COP |
[°C] | [kW] | [kW] | [kW] | [kW] | [kW] | [kW] | [kW] | ||||||||
Máx. | -20 | - | - | 6,5 | 1,76 | 5,7 | 1,46 | - | - | - | - | - | - | - | - |
-15 | - | - | 8,0 | 2,05 | 7,5 | 1,88 | - | - | - | - | - | - | - | - | |
-10 | 10,7 | 2,36 | 10,3 | 2,20 | 9,9 | 2,05 | 9,5 | 1,90 | - | - | - | - | - | - | |
-7 | 11,1 | 2,57 | 11,1 | 2,36 | 11,1 | 2,16 | 11,1 | 1,96 | 10,0 | 1,88 | - | - | - | - | |
2 | 11,6 | 2,87 | 11,3 | 2,62 | 11,1 | 2,37 | 10,8 | 2,12 | 10,7 | 1,91 | 10,6 | 1,71 | - | - | |
7 | 14,2 | 4,38 | 13,8 | 3,93 | 13,4 | 3,48 | 13,0 | 3,03 | 12,8 | 2,67 | 12,5 | 2,31 | - | - | |
12 | 15,4 | 4,81 | 14,9 | 4,31 | 14,5 | 3,81 | 14,0 | 3,31 | 13,8 | 2,91 | 13,5 | 2,51 | - | - | |
15 | 16,0 | 5,08 | 15,5 | 4,55 | 15,0 | 4,01 | 14,5 | 3,48 | 14,3 | 3,05 | 14,0 | 2,62 | - | - | |
20 | 17,5 | 5,64 | 17,1 | 5,06 | 16,7 | 4,48 | 16,3 | 3,90 | 16,2 | 3,46 | 16,1 | 3,02 | - | - | |
Nom. | -20 | - | - | 6,5 | 1,76 | 5,7 | 1,46 | - | - | - | - | - | - | - | - |
-15 | - | - | 8,0 | 2,05 | 7,5 | 1,88 | - | - | - | - | - | - | - | - | |
-10 | 8,0 | 2,63 | 8,0 | 2,42 | 8,0 | 2,20 | 8,0 | 1,99 | - | - | - | - | - | - | |
-7 | 8,0 | 2,99 | 8,0 | 2,72 | 8,0 | 2,44 | 8,0 | 2,16 | 8,0 | 1,94 | - | - | - | - | |
2 | 10,0 | 3,18 | 10,0 | 2,86 | 10,0 | 2,54 | 10,0 | 2,22 | 10,0 | 1,97 | 10,0 | 1,73 | - | - | |
7 | 12,5 | 4,59 | 12,5 | 4,08 | 12,5 | 3,57 | 12,5 | 3,06 | 12,5 | 2,69 | 12,5 | 2,32 | - | - | |
12 | 13,5 | 5,05 | 13,5 | 4,48 | 13,5 | 3,92 | 13,5 | 3,35 | 13,5 | 2,93 | 13,5 | 2,51 | - | - | |
15 | 14,0 | 5,36 | 14,0 | 4,75 | 14,0 | 4,14 | 14,0 | 3,53 | 14,0 | 3,08 | 14,0 | 2,62 | - | - | |
20 | 15,5 | 5,90 | 15,5 | 5,26 | 15,5 | 4,62 | 15,5 | 3,99 | 15,5 | 3,50 | 15,5 | 3,02 | - | - | |
Med. | -20 | - | - | 5,2 | 1,85 | 4,5 | 1,45 | - | - | - | - | - | - | - | - |
-15 | - | - | 6,4 | 2,15 | 6,0 | 1,95 | - | - | - | - | - | - | - | - | |
-10 | 6,4 | 2,79 | 6,4 | 2,54 | 6,4 | 2,29 | 6,4 | 2,04 | - | - | - | - | - | - | |
-7 | 6,4 | 3,05 | 6,4 | 2,77 | 6,4 | 2,49 | 6,4 | 2,21 | 6,4 | 1,96 | - | - | - | - | |
2 | 8,0 | 3,34 | 8,0 | 3,00 | 8,0 | 2,66 | 8,0 | 2,32 | 8,0 | 2,06 | 8,0 | 1,81 | - | - | |
7 | 10,0 | 4,75 | 10,0 | 4,25 | 10,0 | 3,74 | 10,0 | 3,23 | 10,0 | 2,83 | 10,0 | 2,42 | - | - | |
12 | 10,8 | 5,35 | 10,8 | 4,80 | 10,8 | 4,25 | 10,8 | 3,69 | 10,8 | 3,24 | 10,8 | 2,79 | - | - | |
15 | 11,2 | 5,82 | 11,2 | 5,22 | 11,2 | 4,62 | 11,2 | 4,02 | 11,2 | 3,50 | 11,2 | 2,99 | - | - | |
20 | 12,4 | 6,80 | 12,4 | 6,04 | 12,4 | 5,29 | 12,4 | 4,53 | 12,4 | 3,93 | 12,4 | 3,32 | - | - | |
Mín. | -20 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
-15 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
-10 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
-7 | 3,7 | 2,90 | 3,6 | 2,61 | 3,5 | 2,33 | 3,4 | 2,04 | 3,3 | 1,80 | - | - | - | - | |
2 | 3,8 | 3,30 | 4,5 | 3,17 | 4,2 | 2,75 | 4,0 | 2,34 | 3,8 | 2,00 | 3,5 | 1,72 | - | - | |
7 | 3,9 | 4,06 | 3,8 | 3,64 | 3,6 | 3,22 | 3,5 | 2,79 | 3,2 | 2,39 | 3,0 | 1,99 | - | - | |
12 | 4,5 | 5,10 | 4,4 | 4,54 | 4,3 | 3,99 | 4,1 | 3,43 | 3,8 | 2,93 | 3,6 | 2,43 | - | - | |
15 | 4,9 | 6,07 | 4,8 | 5,37 | 4,6 | 4,67 | 4,5 | 3,97 | 4,2 | 3,38 | 3,9 | 2,79 | - | - | |
20 | 5,6 | 7,51 | 5,5 | 6,58 | 5,3 | 5,65 | 5,2 | 4,72 | 4,9 | 4,01 | 4,6 | 3,30 | - | - |
Asegúrese de evitar el rango no disponible durante los desescarches. De lo contrario, la unidad exterior podría no haberse desecho de toda la escarcha y/o el PHEX se podría congelar.
Tipo IU | S/C | |||
---|---|---|---|---|
Hydrobox | EHSC-VM2D | Ficha ErP | ||
Hydrobox Dúo | 200ℓ | EHST20C-VM2D | Ficha ErP | |
Media Tª (55°C) | Clase | A+ | ||
ηs / SCOP | Clima medio | 121% / 3,10 | ||
Clima cálido | 150% / 3,83 | |||
Clima frío | 98% / 2,53 | |||
Baja Tª (35°C) | Clase | A++ | ||
ηs / SCOP | Clima medio | 163% / 4,15 | ||
Clima cálido | 226% / 5,72 | |||
Clima frío | 134% / 3,43 |
Modelo | Etiqueta ErP | ηhw / SCOPdhw6) | ||||
---|---|---|---|---|---|---|
[ℓ] | S/C | Clase | Perfil | Clima medio | Clima cálido | Clima frío |
200 | EHST20C-VM2D | A+ | L | 138% / 3,26 | 156% / 3,67 | 121% / 2,87 |
VKM5
)YKM4
)PKFY-P*VBM
, PFFY-P*VKM
o PFFY-P*VL*
).PKFY-P15/20/25VBM
, PFFY-P20/25/32VKM
, PFFY-P20/25/32VLE(R)M
, PEFY-P-VMA3
y unidades de serie M
, serie S